# -*- coding: utf-8 -*-
# @Author : Paulo Radatz
# @Email : [email protected]
import py_dss_interface
import os
import pathlib
# Getting the absolute directory path of the current script
script_path = os.path.dirname(os.path.abspath(__file__))
# Building the full path to the IEEE 123-bus feeder model
dss_file = pathlib.Path(script_path).joinpath("feeders", "123Bus", "IEEE123Master.dss")
# Instantiating the DSS interface object that allows interaction with OpenDSS
dss = py_dss_interface.DSS()
# Initializing a flag to track when the voltage drops below the threshold (0.95 per unit)
under_voltage = False
# Counter for iteration
i = 0
load_mult = 1
# Start iterating to find the maximum permissible load multiplier without causing undervoltage
while not under_voltage and i < 100: # Stop either when undervoltage is found or after 100 iterations
i = i + 1 # Incrementing the iteration counter
# Calculating the load multiplier as 1 + i/100
load_mult = 1 + i / 100
# OpenDSS commands:
# Reloading the DSS model
dss.text(f"compile [{dss_file}]")
# Creating a new energy meter at Line "L115" in case you want to check the voltage profile commented out below
dss.text("New EnergyMeter.Feeder Line.L115 1")
# Setting the load multiplier (scale factor for system loads)
dss.text(f"set loadmult={load_mult}")
# Solving the distribution power flow for the current conditions
dss.text("solve")
# Plot profile, I would run it in debug mode to plot each profile individually.
# dss.text("Plot profile phases=all")
# Checking the minimum voltage magnitude (in per unit) in all buses of the circuit
if min(dss.circuit.buses_vmag_pu) < 0.95: # If any bus voltage drops below 0.95 pu
under_voltage = True # Set the flag for undervoltage
# Adjust the load multiplier to the value before the last increment (i.e., the last safe value)
load_mult = 1 + (i - 1) / 100
# Once the loop finishes, print the results
if under_voltage: # If the loop stopped due to undervoltage
print(f"The max loadmult: {load_mult}") # Print the maximum safe load multiplier
else: # If the loop reached 100 iterations without causing undervoltage
print(f"No problem with max loadmult of: {load_mult}")