APC AP8886 monitored 0U three-phase 32A PDU

  • Zero-U PDU with no large protrusions
  • 22KW max output (2 x 16A banks on each of 3 phases)
  • Total of 30 x C13 and 12 x C19 outputs split per phase
  • Red 32A 3-phase commando plug on 3M cable

Standard Base Configuration

  • Connect the serial cable that came with the PDU to your serial port
  • Setup your terminal for 9600/8/n/0 no flow-control
  • Power on the PDU and wait for it to boot (15-20 secs)
  • Once the PDU is booted it will show the load on the LCD screen
  • Press return a few times to get a login prompt
  • Login with username/password (apc/apc)
  • Configure IP address, hostname and password
tcpip  -i 10.111.0.97 -s 255.255.0.0 -h pdu1a
user -n admin -pw ********* -pe Administrator -e enable
user -n apc -pw *********
system -n pdu1a
reboot
  • Wait for the PDU to reboot
  • Login again (using the new password)
  • Check the settings have been saved:
tcpip

Getting system information

  • Login to the serial console, and use the "about" command
about

Known issues

  • You can drawer a maximum of 16A per bank; there are six banks in total per PDU.
  • Exceeding 16A will trip the breaker on the bank; PDU must be visited to reset the trip
  • Power Sockets are not labelled on the PDU
  • Default orientation (power cable up) can be reversed, but writing on PDU will be upside down