- Zero-U PDU with no large protrusions
- 22KW max output (2 x 16A banks on each of 3 phases)
- Total of 30 x C13 and 12 x C19 outputs split per phase
- Red 32A 3-phase commando plug on 3M cable
- Connect the serial cable that came with the PDU to your serial port
- Setup your terminal for 9600/8/n/0 no flow-control
- Power on the PDU and wait for it to boot (15-20 secs)
- Once the PDU is booted it will show the load on the LCD screen
- Press return a few times to get a login prompt
- Login with username/password (apc/apc)
- Configure IP address, hostname and password
tcpip -i 10.111.0.97 -s 255.255.0.0 -h pdu1a
user -n admin -pw ********* -pe Administrator -e enable
user -n apc -pw *********
system -n pdu1a
reboot
- Wait for the PDU to reboot
- Login again (using the new password)
- Check the settings have been saved:
tcpip
- Login to the serial console, and use the "about" command
about
- You can drawer a maximum of 16A per bank; there are six banks in total per PDU.
- Exceeding 16A will trip the breaker on the bank; PDU must be visited to reset the trip
- Power Sockets are not labelled on the PDU
- Default orientation (power cable up) can be reversed, but writing on PDU will be upside down